Generator Systems Built to Withstand High Winds
This Information Sheet discusses the special factors and planning that must be considered when supplying generators in enclosures, that are installed outdoors in such regions.
This Information Sheet discusses the special factors and planning that must be considered when supplying generators in enclosures, that are installed outdoors in such regions.
Cooling systems are designed to provide adequate cooling for full load operation at a specified ambient air temperature typically between 40C° (104F°) and 50C° (122F°).
In the installation manual/planning guide they usually specify the air supply duct size, provide exhaust and insulate the combustion exhaust. Gravity louvers will do the job, no forced
In enclosed areas with an engine mounted radiator, expect ambient temperature to increase as the air passes over the genera tor, engine and through the radiator. Table 1 lists the estimated air to core
Factors such as climate and direction of prevailing winds must be considered in an outdoor installation. If your generator is expected to be in temperatures lower than -20 o F (-29 o C) consult the generator
Position the generator set so that the prevailing wind do not enter into the radiator / exhaust outlet. If this is not possible, install a wind barrier. Distance of the wind barrier from the room should be atleast
When discharging air vertically, because the generator is surrounded on all sides, can result in higher than ambient air temperatures being pushed into inlet vents.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recommends that if the operator is also the owner, to read the owner''s manual and thoroughly
The Generac Weather Protected and Sound Attenuated Enclosures will withstand external and internal forces resulting from the above velocity pressure provided the attachment to the mounting surface is